The CSB issues safety recommendations to prevent the recurrence or reduce the likelihood or consequences of similar incidents or hazards in the future. Recommendations are issued to a variety of parties, including government entities, safety organizations, trade unions, trade associations, corporations, emergency response organizations, educational institutions, and public interest groups. Recommendations are published in CSB reports and are closed only by vote of the Board. The CSB tracks all recommendations and communicates regularly with recommendations recipients to ensure that the recommended corrective actions are implemented.

For more information, see Frequently Asked Questions about CSB recommendations.


Quick Search

 
Recommendations Status:
 
 
Expand All

Recommendations

Caribbean Petroleum Refining Tank Explosion and Fire (9 Recommendations)
American Petroleum Institute (API) (3 Recommendations)
Open: 33% | Closed: 67%

Final Report Released On: October 21, 2015

2010-02-I-PR-7

Revise ANSI/API 2350, Overfill Protection for Storage Tanks in Petroleum Facilities (2015), to require the installation of an automatic overfill prevention systems for existing and new facilities at bulk aboveground storage tanks storing gasoline, jet fuel, other fuel mixtures or blendstocks, and other flammable liquids having an NFPA 704 flammability rating of 3 or higher. At a minimum, this system shall meet the following requirements:
a. Separated physically and independent from the level control and monitoring system.
b. Engineered, operated, and maintained to achieve an appropriate safety integrity level in accordance with the requirements of Part 1 of International Electrotechnical Commission (IEC) 61511-SER ed1-2004, Functional Safety – Safety Instrumented Systems for the Process Industry Sector.
c. Specified to achieve the necessary risk reduction as determined by a documented risk assessment methodology set in accordance with Center for Chemical Process Safety Guidelines for Hazard Evaluation Procedures, 3rd Edition, accounting for the following factors:
1. The existence of nearby populations and contamination of nearby environmental resources;
2. The nature and intensity of facility operations;
3. Realistic reliability for the tank gauging system; and
4. The extent/rigor of operator monitoring.
d. Proof tested with sufficient frequency in accordance with the validated arrangements and procedures to maintain the required safety integrity level.
e. Ensure that the above changes are not subject to grandfathering provisions in the standard.

Status: Open - Acceptable Response or Alternate Response
Open - Acceptable Response or Alternate Response (O - ARAR) - Response from recipient indicates a planned action that would satisfy the objective of the recommendation when implemented.
 

PDF Document Recommendation Status Change Summary

2010-02-I-PR-8

Develop detailed guidance on conducting a risk assessment for onsite and offsite impacts of a potential tank overfill during transfer operations involving one and multiple tanks and for determining the Safety Integrity Level of the required overfill prevention safeguard to replace Annex E of ANSI/API 2350, Overfill Protection for Storage Tanks in Petroleum Facilities (2015).

Status: Closed - Acceptable Action
Closed - Acceptable Action (C - AA) - The recipient has completed action on the recommendation. The action taken meets the objectives envisioned by the Board.
 

PDF Document Recommendation Status Change Summary

2010-02-I-PR-9

Develop a single publication or resource describing all API standards and other relevant codes, standards, guidance, and information for filling operations of aboveground storage tanks in petroleum facilities that describes:
a. The required design and management practices for control of filling operations;
b. The minimum set of independent overfill prevention safeguards if the control fails; and
c. Operational challenges (e.g., monitoring/calculating flow rates, ability to maintain constant line pressures, and influences of valve cracking) related to loading multiple tanks concurrently from a single product source.

Status: Closed - Acceptable Alternative Action
Closed - Acceptable Alternative Action (C - AAA)
 

PDF Document Recommendation Status Change

Environmental Protection Agency (EPA) (3 Recommendations)
Open: 33% | Closed: 67%

Final Report Released On: October 21, 2015

2010-02-I-PR-1

(Superseded by 2019-01-I-TX-R8 from the Intercontinental Terminals Company (ITC) report)
 
Revise where necessary the Spill Prevention, Control and Countermeasure (SPCC); Facility Response Plan (FRP); and/or Accidental Release Prevention Program (40 CFR Part 68) rules to prevent impacts to the environment and/or public from spills, releases, fires, and explosions that can occur at bulk aboveground storage facilities storing gasoline, jet fuels, blendstocks, and other flammable liquids having an NFPA 704 flammability rating of 3 or higher.
 
At a minimum, these revisions shall incorporate the following provisions:
 
a) Ensure bulk above ground storage facilities conduct and document a risk assessment that takes into account the following factors:
1. The existence of nearby populations and sensitive environmenls;
2. The nature and intensity of facility operations;
3. Realistic reliability of the tank gauging system; and
4. The extent/rigor of operator monitoring
b) Equip bulk aboveground storage containers/tanks with automatic overfill prevention systems that are physically separate and independent from the lank level control systems.
c) Ensure these automatic overfill prevention systems follow good engineering practices.
d) Engineer, operate, and maintain automatic overfill prevention systems to achieve appropriate safety integrity levels in accordance with good engineering practices, such as Part 1 of lnternational Electro-technical Commission (IEC) 61511-SER ed1.0B-2004, Functional Safety - Safety Instrumented Systems for the Process Industry Sector.
e) Regularly inspect and test automatic overfill prevention systems to ensure their proper operation in accordance with good engineering practice.

Status: Closed - Reconsidered/Superseded
Closed - Reconsidered/Superseded (C - R/S) - Recipient rejects the recommendation and also supports the rejection with a rationale with which the Board concurs. This designation may apply when later facts indicate that the concerns expressed in the recommendation were actually addressed prior to the incident, or when a recommendation is superseded by a new, more appropriate recommendation.
 

PDF Document Recommendation Status Change Summary

2010-02-I-PR-2

Conduct a survey of randomly selected bulk aboveground storage containers storing gasoline or other flammable liquids with a NFPA 704 flammability rating of 3 or higher, at terminals in high risk locations (such as near population centers or sensitive environments) that are already subject to the Spill Prevention, Control and Countermeasure (SPCC) and/or Facility Response Plan (FRP) rules to determine:
a) The nature of the safety management systems in place to prevent overfilling a storage tank during loading operations. Analysis of the safety management systems should include equipment, training, staffing, operating procedures and preventative maintenance programs.
b) The extent to which terminals use independent high level alarms, automated shutoff/diversion systems, redundant level alarms or other technical means to prevent overfilling a tank
c) The history of overfilling incidents at the facilities, with or without consequence
d) Whether additional reporting requirements are needed to understand the types of incidents leading to overfilling spills that breach secondary containment and have the potential to impact the environment and/or the public, as well as the number of safeguards needed to prevent them.

Status: Closed - Acceptable Alternative Action
Closed - Acceptable Alternative Action (C - AAA)
 

PDF Document Recommendation Status Change Summary

2010-02-I-PR-3

As an interim measure, until the rule changes in CSB Recommendation No. 2010-02-I-PR-R1 are adopted and go into effect: issue appropriate guidance or an alert, similar to EPA’s previously issued Chemical Safety Alert addressing Rupture Hazard from Liquid Storage Tanks, to illustrate the hazards posed by spills, releases, fires and explosions due to overfilling bulk aboveground storage containers storing gasoline, jet fuel, blendstocks, and other flammable liquids having an NFPA 704 flammability rating of 3 or higher.

Status: Open - Acceptable Response or Alternate Response
Open - Acceptable Response or Alternate Response (O - ARAR) - Response from recipient indicates a planned action that would satisfy the objective of the recommendation when implemented.
 

PDF Document Recommendation Status Change Summary

International Code Council (ICC) (1 Recommendations)
Open: 100% | Closed: 0%

Final Report Released On: October 21, 2015

2010-02-I-PR-5

Revise the Section 5704.2.7.5.8 (2015), Overfill Prevention of the International Fire Code (IFC) to require an automatic overfill prevention system (AOPS) for bulk aboveground storage tank terminals storing gasoline, jet fuel, other fuel mixtures or blendstocks, and other flammable liquids having an NFPA 704 flammability rating of 3 or higher, or equivalent designation. These safeguards shall meet the following requirements:
a) Engineered, operated, and maintained to achieve an appropriate safety integrity level in accordance with the requirements of Part 1 of International Electrotechnical Commission (IEC) 61511-SER ed1-2004, Functional Safety – Safety Instrumented Systems for the Process Industry Sector.
b) Specified to achieve the necessary risk reduction as determined by a documented risk assessment methodology in accordance with Center for Chemical Process Safety Guidelines for Hazard Evaluation Procedures, 3rd Edition, accounting for the following factors:
i. The existence of nearby populations and sensitive environments;
ii. The nature and intensity of facility operations;
iii. Realistic reliability for the tank gauging system; and
iv. The extent/rigor of operator monitoring.
c) Proof tested in accordance with the validated arrangements and procedures with sufficient frequency to maintain the specified safety integrity level.
d) Ensure that the above changes are not subject to grandfathering provisions in the codes.

Status: Open - Awaiting Response or Evaluation/Approval of Response
Open - Awaiting Response or Evaluation/Approval of Response (O - ARE/AR) - The recipient has not submitted a substantive response, or the evaluation by CSB staff of a response is pending, or the Board has not yet acted on staff recommendation of status.
 

National Fire Protection Association (NFPA) (1 Recommendations)
Open: 0% | Closed: 100%

Final Report Released On: October 21, 2015

2010-02-I-PR-6

Revise NFPA 30, Storage of Flammable and Combustible Liquids, Section 21.7.1.1 (2015) for bulk aboveground storage tank terminals storing gasoline, jet fuel, other fuel mixtures or blendstocks, and other flammable liquids having an NFPA 704 flammability rating of 3 or greater. This modification shall meet the following requirements:
a. More than one safeguard to prevent a tank overfill, all within an automatic overfill prevention system as described in ANSI/API Standard 2350 (2015) Overfill Protection for Storage Tanks in Petroleum Facilities with an independent level alarm as one of the safeguards. The safeguards should meet the following standards:
1. Separated physically and electronically and independent from the tank gauging system;
2. Engineered, operated, and maintained for an appropriate level of safety based on the predetermined risk level after considering part b of this recommendation; and
3. Proof tested with sufficient frequency in accordance with the validated arrangements and procedures.
b. Specified to achieve the necessary risk reduction as determined by a documented risk assessment methodology conducted in accordance with Center for Chemical Process Safety Guidelines for Hazard Evaluation Procedures, 3rd Edition, accounting for the following factors:
1. The existence of nearby populations and contamination of nearby environmental resources;
2. The nature and intensity of facility operations;
3. Realistic reliability for the tank gauging system; and
4. The extent/rigor of operator monitoring.
c. Ensure that the above changes not subject to grandfathering provisions in the code.

Status: Closed - Reconsidered/Superseded
Closed - Reconsidered/Superseded (C - R/S) - Recipient rejects the recommendation and also supports the rejection with a rationale with which the Board concurs. This designation may apply when later facts indicate that the concerns expressed in the recommendation were actually addressed prior to the incident, or when a recommendation is superseded by a new, more appropriate recommendation.
 

PDF Document Recommendation Status Change Summary

Occupational Safety and Health Administration (OSHA) (1 Recommendations)
Open: 0% | Closed: 100%

Final Report Released On: October 21, 2015

2010-02-I-PR-4

(Superseded by 2019-01-I-TX-R7 from the Intercontinental Terminals Company (ITC) report)
 
a) Revise the Flammable and Combustible Liquids standard (29 CFR§ 1910.106) to require installing, using, and maintaining a high-integrity automatic overfill prevention system with a means of level detection, logic/control equipment, and independent means of flow control for bulk aboveground storage tanks containing gasoline, jet fuel, other fuel mixtures or blends tocks, and other flammable liquids having an NFPA 704 flammability rating of 3 or higher, to protect against loss of containment. At a minimum, this system
shall meet the following requirements:
1. Separated physically and electronically and independent from the tank gauging system.
2. Engineered, operated, and maintained to achieve an appropriate level of safety integrity in accordance with the rrequirements of Part 1 of International Electro-technical Commission (IEC) 61511-SER ed1.0B-2004, Functional Safety - Safety Instrumented Systems for the Process Industry Sector. Such a system would employ a safety integrity level (SIL) documented in accordance with the principles in Part 3 of IEC 61511-SER ed1.0B-2004, accounting for the following factors:
i. The existence of nearby populations and sensitive environments;
ii. The nature and intensity of facility operations;
iv. The extent/ rigor of operator monitoring.
3. Proof tested in accordance with the validated arrangements and procedures with sufficient frequency to ensure the specified safety integrity level is maintained.
b) Establish hazard analysis, management of change and mechanical integrity management system elements for bulk above ground storage tanks in the revised 1910.106 standard that are similar to those in the Process Safety Management of Highly Hazardous Chemicals standard (29 CFR § 1910.119) and ensure these facilities are subject to Recognized and Generally Accepted Good Engineering Practices (RAGAGEP).

Status: Closed - Reconsidered/Superseded
Closed - Reconsidered/Superseded (C - R/S) - Recipient rejects the recommendation and also supports the rejection with a rationale with which the Board concurs. This designation may apply when later facts indicate that the concerns expressed in the recommendation were actually addressed prior to the incident, or when a recommendation is superseded by a new, more appropriate recommendation.
 

PDF Document Recommendation Status Change Summary

Chevron Richmond Refinery Fire (37 Recommendations)
American Petroleum Institute (API) (6 Recommendations)
Open: 33% | Closed: 67%

Final Report Released On: January 28, 2015

2012-03-I-CA-26

Revise API RP 939-C: Guidelines for Avoiding Sulfidation (Sulfidic) Corrosion Failures in Oil Refineries to establish minimum requirements for preventing catastrophic rupture of low-silicon carbon steel piping.  At a minimum: 

a.       Require users to identify carbon steel piping circuits susceptible to sulfidation corrosion that may contain low-silicon components.  These circuits have the potential to contain carbon steel components that were not manufactured to the American Society for Testing and Materials (ASTM) A106 specification and may contain less than 0.10 weight percent silicon content. 

b.      For piping circuits identified to meet the specifications detailed in 2012-03-I-CA-R26(a), require users to either (1) enact a program to inspect every component within the piping circuit once, known as 100 percent component inspection (per the requirements established pursuant to recommendation 2012-03-I-CA-R28(c)), or (2) replace the identified at-risk carbon steel piping with a steel alloy that is more resistant to sulfidation corrosion. 

c.       If low-silicon components or components with accelerated corrosion are identified in a carbon steel piping circuit meeting the specifications detailed in 2012-03-I-CA-R26(a), require designation of these components as permanent Condition Monitoring Locations (CMLs) until the piping components are replaced.


Status: Closed - Acceptable Alternative Action
Closed - Acceptable Alternative Action (C - AAA)
 

PDF Document Recommendation Status Change

2012-03-I-CA-27

Revise API RP 571: Damage Mechanisms Affecting Fixed Equipment in the Refining Industry to:

a.       Describe the potential for increased rates of sulfidation corrosion occurring in low-silicon carbon steel in Section 4.4.2.3 Critical Factors

b.      Specify that sulfidation corrosion rates in carbon steel piping can be significantly faster in a few, individual piping components in section 4.4.2.5 Appearance or Morphology of Damage; and

c.       Refer the reader to the 100 percent component inspection or pipe replacement requirements detailed in API RP 939-C: Guidelines for Avoiding Sulfidation (Sulfidic) Corrosion Failures in Oil Refineries (pursuant to recommendation 2012-03-I-CA-R26)  and API 570: Piping Inspection Code:  In-service Inspection, Rating, Repair, and Alteration of Piping Systems (pursuant to 2012-03-I-CA-R28(c)) for carbon steel piping circuits susceptible to sulfidation corrosion that may contain low-silicon components.  


Status: Closed - Acceptable Action
Closed - Acceptable Action (C - AA) - The recipient has completed action on the recommendation. The action taken meets the objectives envisioned by the Board.
 

PDF Document Recommendation Status Change Summary

2012-03-I-CA-28

Revise API 570: Piping Inspection Code:  In-service Inspection, Rating, Repair, and Alteration of Piping Systems to:   

 

a.       Use terminology consistent with API RP 939-C: Guidelines for Avoiding Sulfidation (Sulfidic) Corrosion Failures in Oil Refineries and other API standards and recommended practices discussed in this report.  Replace the terminology “high-temperature sulfur corrosion” with “sulfidation corrosion”;

b.      Specify that sulfidation corrosion rates in carbon steel piping can be significantly faster in some individual piping components than in others;

c.       Establish a new section that details inspection requirements to identify low-silicon piping components in carbon steel circuits susceptible to sulfidation corrosion.  This section shall require users to identify carbon steel piping circuits at risk to contain low-silicon components by following the requirements detailed in API RP 939-C: Guidelines for Avoiding Sulfidation (Sulfidic) Corrosion Failures in Oil Refineries (pursuant to 2012-03-I-CA-R26(a)) and API RP 578: Material Verification Program for New and Existing Alloy Piping Systems (pursuant to 2012-03-I-CA-R29).  At a minimum, require users to either:

                                                              i.      Inspect every component within all carbon steel piping circuits susceptible to sulfidation corrosion that may contain low-silicon components once.  The purpose of this practice is to identify any low-silicon components that are corroding at accelerated rates.  Inspection may be performed through ultrasonic thickness measurements to establish corrosion rates for each component, destructive laboratory analysis, or other methods.  Following the inspection, require users to follow the low-silicon corrosion rate monitoring requirements established in 2012-03-I-CA-R26(c); or    

                                                            ii.      Replace the identified at-risk carbon steel piping with a steel alloy that is more resistant to sulfidation corrosion.

 

d.      Incorporate as a “normative reference” API RP 939-C: Guidelines for Avoiding Sulfidation (Sulfidic) Corrosion Failures in Oil Refineries; and

e.       Require users to follow the minimum leak response guidance establishedinAPI RP 2001: Fire Protection in Refineries, developed in response to recommendation 2012-03-I-CA-R31.


Status: Closed - Acceptable Action
Closed - Acceptable Action (C - AA) - The recipient has completed action on the recommendation. The action taken meets the objectives envisioned by the Board.
 

PDF Document Download

2012-03-I-CA-29

Revise API RP 578: Material Verification Program for New and Existing Alloy Piping Systems, to require users to establish and implement a program to identify carbon steel piping circuits that are susceptible to sulfidation corrosionand may contain low-silicon components.  These circuits have the potential to contain carbon steel components that were not manufactured to the American Society for Testing and Materials (ASTM) A106 specification and may contain less than 0.10 weight percent silicon content.  Refer the reader to the 100 percent component inspection or pipe replacement requirements detailed in API RP 939-C: Guidelines for Avoiding Sulfidation (Sulfidic) Corrosion Failures in Oil Refineries (pursuant to recommendation 2012-03-I-CA-26(b))  and API 570: Piping Inspection Code:  In-service Inspection, Rating, Repair, and Alteration of Piping Systems (pursuant to 2012-03-I-CA-28(c)) for carbon steel piping circuits susceptible to sulfidation corrosion that may contain low-silicon components.


Status: Open - Awaiting Response or Evaluation/Approval of Response
Open - Awaiting Response or Evaluation/Approval of Response (O - ARE/AR) - The recipient has not submitted a substantive response, or the evaluation by CSB staff of a response is pending, or the Board has not yet acted on staff recommendation of status.
 

2012-03-I-CA-30

Revise API RP 574: Inspection Practices for Piping System Components (3rd edition) to: 

a.       Incorporate as a normative reference API RP 939-C: Guidelines for Avoiding Sulfidation (Sulfidic) Corrosion Failures in Oil Refineries;

b.      Reference API RP 939-C: Guidelines for Avoiding Sulfidation (Sulfidic) Corrosion Failures in Oil Refineries when discussing that nonsilicon-killed carbon steel is susceptible to sulfidation corrosion; and

c.       In Section 9.3 Investigation of Leaks, require users to follow the leak response protocol requirements established in API RP 2001: Fire Protection in Refineries (pursuant to 2012-03-I-CA-R31).


Status: Closed - Acceptable Alternative Action
Closed - Acceptable Alternative Action (C - AAA)
 

PDF Document Recommendations Status Change Summary

2012-03-I-CA-31

Revise API RP 2001: Fire Protection in Refineries to require users to develop a process fluid leak response protocol specific to their own facility that must be followed when a process fluid leak is discovered.  Recommend users to incorporate the following actions into their leak response protocol: 

a.       Establish an Incident Command structure upon identification of a process fluid leak;

b.      Conduct a pre-response meeting with personnel with specific technical expertise (e.g., inspectors, operators, metallurgists, engineers, and management) and the Incident Commander to determine pressure, temperature, remaining inventory of process fluids, potential damage mechanisms that caused the leak, and worst-case leak scenario;

c.       Establish a hot zone that identifies the area of risk of exposure or injuries due to flame contact, radiant heat, or contact to hazardous materials, taking into consideration the worst-case leak scenario;

d.      Limit site access around leak location to essential personnel only;

e.       Isolate the leaking piping or vessel, or if isolation is not possible, shutdown of the unit when the leaking process fluid poses immediate danger to safety, health, or the environment—such as piping fluid that is toxic or near the autoignition temperature.


Status: Open - Awaiting Response or Evaluation/Approval of Response
Open - Awaiting Response or Evaluation/Approval of Response (O - ARE/AR) - The recipient has not submitted a substantive response, or the evaluation by CSB staff of a response is pending, or the Board has not yet acted on staff recommendation of status.
 

American Society of Mechanical Engineers (ASME) (1 Recommendations)
Open: 100% | Closed: 0%

Final Report Released On: January 28, 2015

2012-03-I-CA-32

Revise ASME PCC-2-2011: Repair of Pressure Equipment and Piping to require users to follow the minimum process fluid leak response requirements established in API RP 2001: Fire Protection in Refineries, developed in response to recommendation 2012-03-I-CA-R31, before conducting process fluid leak repair.


Status: Open - Acceptable Response or Alternate Response
Open - Acceptable Response or Alternate Response (O - ARAR) - Response from recipient indicates a planned action that would satisfy the objective of the recommendation when implemented.
 

PDF Document Recommendation Status Change Summary

Board of Supervisors, Contra Costa County, CA (6 Recommendations)
Open: 0% | Closed: 100%

Final Report Released On: January 28, 2015

2012-03-I-CA-6

Revise the Industrial Safety Ordinance (ISO) to require that Process Hazard Analyses include documentation of the recognized methodologies, rationale and conclusions used to claim that safeguards intended to control hazards will be effective. This process shall use established qualitative, quantitative, and/or semi-quantitative methods such as Layers of Protection Analysis (LOPA).


Status: Closed - Acceptable Alternative Action
Closed - Acceptable Alternative Action (C - AAA)
 

PDF Document Recommendations Status Change Summary

2012-03-I-CA-7

Revise the Industrial Safety Ordinance (ISO) to require the documented use of inherently safer systems analysis and the hierarchy of controls to the greatest extent feasible in establishing safeguards for identified process hazards. The goal shall be to drive the risk of major accidents to As Low As Reasonably Practicable (ALARP). Include requirements for inherently safer systems analysis to be automatically triggered for all Management of Change and Process Hazard Analysis reviews, prior to the construction of new processes, process unit rebuilds, significant process repairs, and in the development of corrective actions from incident investigation recommendations.


Status: Closed - Acceptable Alternative Action
Closed - Acceptable Alternative Action (C - AAA)
 

PDF Document Recommendations Status Change Summary

2012-03-I-CA-8

Monitor and confirm the effective implementation of the damage mechanism hazard review program (2012-03-I-CA-R1 and 2012-03-I-CA-R2), so that all necessary mechanical integrity work at the Chevron Richmond Refinery is identified and recommendations are completed in a timely way.


Status: Closed - Acceptable Action
Closed - Acceptable Action (C - AA) - The recipient has completed action on the recommendation. The action taken meets the objectives envisioned by the Board.
 

PDF Document Recommendation Status Change Summary

2012-03-I-CA-16

Participate in the joint regulatory program described in recommendation 2012-03-I-CA-R11. This participation shall include contributing relevant data to the repository of investigation and inspection data created by the California Department of Industrial Relations and jointly coordinating activities.


Status: Closed - Acceptable Action
Closed - Acceptable Action (C - AA) - The recipient has completed action on the recommendation. The action taken meets the objectives envisioned by the Board.
 

PDF Document Status Change Summary

2012-03-I-CA-25

Implement a compensation system to ensure the regulator has the ability to attract and retain a sufficient number of employees with the necessary skills and experience to ensure regulator technical competency at all levels of process safety regulatory oversight and policy development in Contra Cost County, California. A market analysis and benchmarking review should be periodically conducted to ensure the compensation system remains competitive with California petroleum refineries.


Status: Closed - Acceptable Action
Closed - Acceptable Action (C - AA) - The recipient has completed action on the recommendation. The action taken meets the objectives envisioned by the Board.
 

PDF Document Recommendations Status Change Summary

2012-03-I-CA-36

Revise the Industrial Safety Ordinance (ISO) regulations for petroleum refineries to require a process safety culture continuous improvement program including a written procedure for periodic process safety culture surveys across the work force. Require an oversight committee comprised of the regulator, the company, the company’s workforce and their representatives, and community representatives. This oversight committee shall:

a. Select an expert third party that will administer a periodic process safety culture survey;

b. Review and comment on the third party expert report developed from the survey;

c. Oversee the development and effective implementation of action items to effectively address identified process safety culture issues; and

d. Develop process safety culture indicators to measure major accident prevention performance.

The periodic process safety culture report shall be made available to the plant workforce.


Status: Closed - Acceptable Alternative Action
Closed - Acceptable Alternative Action (C - AAA)
 

PDF Document Recommendation Status Change Summary

California Air Quality Management Divisions (1 Recommendations)
Open: 0% | Closed: 100%

Final Report Released On: January 28, 2015

2012-03-I-CA-18

Participate in the joint regulatory program described in recommendation 2012-03-I-CA-R11. This participation shall include contributing relevant data to the repository of investigation and inspection data created by the California Department of Industrial Relations and jointly coordinating activities.


Status: Closed - Acceptable Action
Closed - Acceptable Action (C - AA) - The recipient has completed action on the recommendation. The action taken meets the objectives envisioned by the Board.
 

PDF Document Status Change Summary

California Environment Protection Agency (Cal/EPA) (1 Recommendations)
Open: 0% | Closed: 100%

Final Report Released On: January 28, 2015

2012-03-I-CA-20

Participate in the joint regulatory program described in recommendation 2012-03-I-CA-R11. This participation shall include contributing relevant data to the repository of investigation and inspection data created by the California Department of Industrial Relations and jointly coordinating activities.


Status: Closed - Exceeds Recommended Action
Closed - Exceeds Recommended Action (C - ERA) - Action on the recommendation meets and surpasses the objectives envisioned by the Board.
 

PDF Document Status Change Summary

Chevron USA (5 Recommendations)
Open: 0% | Closed: 100%

Final Report Released On: January 28, 2015

2012-03-I-CA-1 URGENT!

At all Chevron U.S. refineries, engage a diverse team of qualified personnel to perform a documented damage mechanism hazard review. This review shall be an integral part of the Process Hazard Analysis cycle and shall be conducted on all PSM-covered process piping circuits and process equipment. The damage mechanism hazard review shall identify potential process damage mechanisms and consequences of failure, and shall ensure safeguards are in place to control hazards presented by those damage mechanisms. Analyze and incorporate into this review applicable industry best practices, Chevron Energy Technology Company findings and recommendations, and inherently safer systems to the greatest extent feasible.


Status: Closed - Acceptable Action
Closed - Acceptable Action (C - AA) - The recipient has completed action on the recommendation. The action taken meets the objectives envisioned by the Board.
 

PDF Document Recommendations Status Change Summary

2012-03-I-CA-2 URGENT!

At all California Chevron U.S. refineries, report leading and lagging process safety indicators, such as the action item completion status of recommendations from damage mechanism hazard reviews, to the federal, state, and local regulatory agencies that have chemical release prevention authority.


Status: Closed - Acceptable Alternative Action
Closed - Acceptable Alternative Action (C - AAA)
 

PDF Document Recommendation Status Change

2012-03-I-CA-33

Develop a method to assign accountability at Chevron to determine whether any whether any new Energy Technology Company (ETC) recommended program or industry best practice, such as API guidance must be followed to ensure process safety or employee personal safety.  This method shall include monitoring of these practices and guidance at a refining system level and at the refinery level.  Develop a tracking system to monitor the progress of implementing these selected practices and guidance to completion.


Status: Closed - Acceptable Action
Closed - Acceptable Action (C - AA) - The recipient has completed action on the recommendation. The action taken meets the objectives envisioned by the Board.
 

PDF Document Recommendations Status Change Summary

2012-03-I-CA-34

Develop an auditable process to be available for all recommended turnaround work items necessary to address mechanical integrity deficiencies or inspection recommendations that are denied or deferred.  This process shall provide the submitter of the denied or deferred recommendation with the option to seek further review by his or her manager, who can further elevate and discuss the recommendation with higher level management, such as the Area Business Unit Manager.  Maintain an auditable log of each of these potential turnaround work items, including the ultimate determination of approval, deferral, or rejection, justification determination, and the person or team responsible for that decision.


Status: Closed - Acceptable Action
Closed - Acceptable Action (C - AA) - The recipient has completed action on the recommendation. The action taken meets the objectives envisioned by the Board.
 

PDF Document Recommendations Status Change Summary

2012-03-I-CA-35

Develop an approval process that includes a technical review that must be implemented prior to resetting the minimum alert thickness to a lower value in the inspection database.


Status: Closed - Acceptable Action
Closed - Acceptable Action (C - AA) - The recipient has completed action on the recommendation. The action taken meets the objectives envisioned by the Board.
 

PDF Document Recommendations Status Change Summary

Environmental Protection Agency (EPA) (2 Recommendations)
Open: 0% | Closed: 100%

Final Report Released On: January 28, 2015

2012-03-I-CA-15

Jointly plan and conduct inspections with Cal/OSHA, California EPA and other state and local regulatory agencies with chemical accident prevention responsibilities to monitor the effective implementation of the damage mechanism hazard review and disclosure requirements under 2012-03-I-CA-R9 and R10 above.


Status: Closed - Acceptable Alternative Action
Closed - Acceptable Alternative Action (C - AAA)
 

PDF Document Recommendation Status Change Summary

2012-03-I-CA-19

Participate in the joint regulatory program described in recommendation 2012-03-I-CA-R11. This participation shall include contributing relevant data to the repository of investigation and inspection data created by the California Department of Industrial Relations and jointly coordinating activities.


Status: Closed - Acceptable Action
Closed - Acceptable Action (C - AA) - The recipient has completed action on the recommendation. The action taken meets the objectives envisioned by the Board.
 

PDF Document Status Change Summary

Governor and Legislature of the State of California (9 Recommendations)
Open: 11% | Closed: 89%

Final Report Released On: January 28, 2015

2012-03-I-CA-9

Revise the California Code of Regulations, Title 8, Section 5189, Process Safety Management of Acutely Hazardous Materials, to require improvements to mechanical integrity and process hazard analysis programs for all California oil refineries. These improvements shall include engaging a diverse team of qualified personnel to perform a documented damage mechanism hazard review. This review shall be an integral part of the Process Hazard Analysis cycle and shall be conducted on all PSM-covered process piping circuits and process equipment. The damage mechanism hazard review shall identify potential process damage mechanisms and consequences of failure, and shall ensure safeguards are in place to control hazards presented by those damage mechanisms. Require the analysis and incorporation of applicable industry best practices and inherently safety systems to the greatest extent feasible into this review.


Status: Closed - Acceptable Action
Closed - Acceptable Action (C - AA) - The recipient has completed action on the recommendation. The action taken meets the objectives envisioned by the Board.
 

PDF Document Recommendations Status Change Summary

2012-03-I-CA-10

For all California oil refineries, identify and require the reporting of leading and lagging process safety indicators, such as the action item completion status of recommendations from damage mechanism hazard reviews, to state and local regulatory agencies that have chemical release prevention authority. These indicators shall be used to ensure that requirements described in 2012-03-I-CA-R9 are effective at improving mechanical integrity and process hazard analysis performance at all California oil refineries and preventing major chemical incidents.


Status: Closed - Acceptable Alternative Action
Closed - Acceptable Alternative Action (C - AAA)
 

PDF Document Recommendations Status Change Summary

2012-03-I-CA-11

Establish a multi-agency process safety regulatory program for all California oil refineries to improve the public accountability, transparency, and performance of chemical accident prevention and mechanical integrity programs. This program shall:

  1. Establish a system to report to the regulator the recognized methodologies, findings, conclusions and corrective actions related to refinery mechanical integrity inspection and repair work arising from Process Hazard Analyses, California oil refinery turnarounds and maintenance-related shutdowns;
  2. Require reporting of information such as damage mechanism hazard reviews, notice of upcoming maintenance-related shutdowns, records related to proposed and completed mechanical integrity work lists, and the technical rationale for any delay in work proposed but not yet completed;
  3. Establish procedures for greater workforce and public participation including the public reporting of information; and
  4. Provide mechanisms for federal, state and local agency operational coordination, sharing of data (including safety indicator data), and joint accident prevention activities. The California Department of Industrial Relations will be designated as the lead state agency for establishing a repository of joint investigative and inspection data, coordinating the sharing of data and joint accident prevention activities.

Status: Closed - Acceptable Alternative Action
Closed - Acceptable Alternative Action (C - AAA)
 

PDF Document Recommendations Status Change Summary

2012-03-I-CA-12

Require that Process Hazard Analyses required under California Code of Regulations, Title 8, Section 5189 Section (e) include documentation of the recognized methodologies, rationale and conclusions used to claim that safeguards intended to control hazards will be effective. This process shall use established qualitative, quantitative, and/or semi-quantitative methods such as Layers of Protection Analysis (LOPA).


Status: Closed - Acceptable Action
Closed - Acceptable Action (C - AA) - The recipient has completed action on the recommendation. The action taken meets the objectives envisioned by the Board.
 

PDF Document Recommendations Status Change Summary

2012-03-I-CA-13

Require the documented use of inherently safer systems analysis and the hierarchy of controls to the greatest extent feasible in establishing safeguards for identified process hazards. The goal shall be to drive the risk of major accidents to As Low As Reasonably Practicable (ALARP). Include requirements for inherently safer systems analysis to be automatically triggered for all Management of Change and Process Hazard Analysis reviews, prior to the construction of new process, process unit rebuilds, significant process repairs and in the development of corrective actions from incident investigation recommendations.


Status: Closed - Acceptable Alternative Action
Closed - Acceptable Alternative Action (C - AAA)
 

PDF Document Recommendations Status Change Summary

2012-03-I-CA-14

Monitor and confirm the effective implementation of the damage mechanism hazard review program (2012-03-I-CA-R9 and 2012-03-I-CA-R10), so that all necessary mechanical integrity work at all California Chevron Refineries is identified and recommendations are completed in a timely way.


Status: Closed - Acceptable Alternative Action
Closed - Acceptable Alternative Action (C - AAA)
 

PDF Document Recommendations Status Change Summary

2012-03-I-CA-21

Based on the findings in this report, enhance and restructure California’s process safety management (PSM) regulations for petroleum refineries by including the following goal-setting attributes:

a. Require a comprehensive process hazard analysis (PHA) written by the company that includes:

i. Systematic analysis and documentation of all major hazards and safeguards, using the hierarchy of controls to identify hazards and significantly reduce risks to a goal of as low as reasonably practicable (ALARP) or similar;

ii. Documentation of the recognized methodologies, rationale and conclusions used to claim that inherently safer systems have been implemented to as low as reasonably practicable (ALARP) or similar, and that additional safeguards intended to control remaining hazards will be effective;

iii. Documented damage mechanism hazard review conducted by a diverse team of qualified personnel. This review shall be an integral part of the process hazard analysis (PHA) cycle and shall be conducted on all covered processes, piping circuits and equipment. The damage mechanism hazard review shall identify potentia process damage mechanisms and consequences of failure, and shall ensure effective safeguards are in place to prevent or control hazards presented by those damage mechanisms. Require the analysis and incorporation of applicable industry best practices and inherently safer design to the greatest extent feasible into this review; and

iv. Documented use of inherently safer systems analysis and the hierarchy of controls to the greatest extent feasible in establishing safeguards for identified process hazards. The goal shall be to drive the risk of major accidents to As Low As Reasonably Practicable (ALARP) or similar. Include requirements for inherently safer systems analysis to be automatically triggered for all management of change (MOC) and process hazard analysis (PHA) reviews, as well as prior to the construction of new processes, process unit rebuilds, significant process repairs, and in the development of corrective actions from incident investigation recommendations.

b. Require a thorough review of the comprehensive process hazard an alysis by technically competent regulatory personnel;

c. Require preventative audits and preventative inspections by the regulator to ensure the effective implementation of the comprehensive process hazard analysis (PHA);

d. Require that all safety codes, standards, employer internal procedures and recognized and generally accepted good engineering practices (RAGAGEP) used in the implementation of the regulations contain adequate minimum requirements;

e. Require mechanisms for the regulator, the refinery, and workers and their representatives to play an equal and essential role in the direction of preventing major incidents. Require an expanded role for workers in management of process safety by establishing the rights and responsibilities of workers and their representatives on health and safety-related matters, and the election of safety representatives and establishment of safety committees (with equal representation between management and labor) to serve health and safety-related functions. The elected representatives should have a legally recognized role that goes beyond consultation in activities such as the development of the comprehensive process hazard analysis, implementation of corrective actions generated from hierarchy of control analyses, management of change, incident investigation, audits, and the identification, prevention, and control of all processhazards. The regulation should provide workers and their representatives with the authority to stop work that is perceived to be unsafe until the employer resolves the matter or the regulator intervenes.  Workforce participation practices should be documented by the refinery to the regulator;

f. Require reporting of information to the public to the greatest extent feasible, such as a summary of the comprehensive process hazard analysis (PHA) which should include a list of inherently safer systems implemented; safeguards implemented for remaining hazards; standards utilized to reduce risks to As Low As Reasonably Practicable (ALARP) or similar; and process safety indicators that demonstrate the effectiveness of the safeguards and management systems;

g. Implement an approach or system that determines when new or improved industry standards and practices are needed and initiate programs and other activities, such as an advisory committee or forum, toprompt the timely development and implementation of such standards and practices; and

h. Ensure that a means of sustained funding is established to support an independent, well-funded, well-staffed, technically competent regulator.


Status: Closed - Acceptable Alternative Action
Closed - Acceptable Alternative Action (C - AAA)
 

PDF Document Recommendation Status Change Summary

2012-03-I-CA-22

Implement a compensation system to ensure the regulator has the ability to attract and retain a sufficient number of employees with the necessary skills and experience to ensure regulator technical competency at all levels of process safety regulatory oversight and policy development in California. A market analysis and benchmarking review should be periodically conducted to ensure the compensation system remains competitive with California petroleum refineries.

 


Status: Closed - Acceptable Action
Closed - Acceptable Action (C - AA) - The recipient has completed action on the recommendation. The action taken meets the objectives envisioned by the Board.
 

PDF Document Recommendation Status Change Summary

2012-03-I-CA-23

Work with the regulator, the petroleum refining industry, labor, and other relevant stakeholders in the state of California to develop and implement a systemthat collects, tracks, and analyzes process safety leading and lagging indicators from refineries and contractors to promote continuous safety improvements. At a minimum, this program shall:

a. Require the use of leading and lagging process safety indicators to actively monitor the effectiveness of process safety management systems and safeguards for major accident prevention. Include leading and lagging indicators that are measureable, actionable, and standardized. Require that the reported data be used for continuous process safety improvement and accident prevention;

b. Analyze data to identify trends and poor performers and publish annual reports with the data at facility and corporate levels;

c. Require companies to publicly report required indicators annually at facility and corporate levels;

d. Use process safety indicators (1) to drive continuous improvement for major accident prevention by using the data to identify industry and facility safety trends and deficiencies and (2) to determine appropriate allocation of regulator resources and inspections; and

e. Be periodically updated to incorporate new learning from world-wide industry improvements in order to drive continuous major accident safety improvements in California.


Status: Open - Acceptable Response or Alternate Response
Open - Acceptable Response or Alternate Response (O - ARAR) - Response from recipient indicates a planned action that would satisfy the objective of the recommendation when implemented.
 

PDF Document Recommendation Status Change Summary

Mayor and City Council, City of Richmond, CA (6 Recommendations)
Open: 0% | Closed: 100%

Final Report Released On: January 28, 2015

2012-03-I-CA-3

Revise the Industrial Safety Ordinance (ISO) to require that Process Hazard Analyses include documentation of the recognized methodologies, rationale and conclusions used to claim that safeguards intended to control hazards will be effective. This process shall use established qualitative, quantitative, and/or semi-quantitative methods such as Layers of Protection Analysis (LOPA).


Status: Closed - Acceptable Alternative Action
Closed - Acceptable Alternative Action (C - AAA)
 

PDF Document Recommendations Status Change Summary

2012-03-I-CA-4

Revise the Industrial Safety Ordinance (ISO) to require the documented use of inherently safer systems analysis and the hierarchy of controls to the greatest extent feasible in establishing safeguards for identified process hazards. The goal shall be to drive the risk of major accidents to As Low As Reasonably Practicable (ALARP). Include requirements for inherently safer systems analysis to be automatically triggered for all Management of Change and Process Hazard Analysis reviews, prior to the construction of new processes, process unit rebuilds, significant process repairs, and in the development of corrective actions from incident investigation recommendations.


Status: Closed - Acceptable Alternative Action
Closed - Acceptable Alternative Action (C - AAA)
 

PDF Document Recommendations Status Change Summary

2012-03-I-CA-5

Ensure the effective implementation of the damage mechanism hazard review program (2012-03-I-CA-R1 and 2012-03-I-CA-R2), so that all necessary mechanical integrity work at the Chevron Richmond Refinery is identified and recommendations are completed in a timely way


Status: Closed - Acceptable Action
Closed - Acceptable Action (C - AA) - The recipient has completed action on the recommendation. The action taken meets the objectives envisioned by the Board.
 

PDF Document Recommendations Status Change Summary

2012-03-I-CA-17

Participate in the joint regulatory program described in recommendation 2012-03-I-CA-R11. This participation shall include contributing relevant data to the repository of investigation and inspection data created by the California Department of Industrial Relations and jointly coordinating activities.


Status: Closed - Acceptable Action
Closed - Acceptable Action (C - AA) - The recipient has completed action on the recommendation. The action taken meets the objectives envisioned by the Board.
 

PDF Document Status Change Summary

2012-03-I-CA-24

Implement or cause to be implemented a compensation system to ensure the regulator has the ability to attract and retain a sufficient number of employees with the necessary skills and experience to ensure regulator technical competency at all levels of process safety regulatory oversight and policy development in Richmond, California. A market analysis and benchmarking review should be periodically conducted to ensure the compensation system remains competitive with California petroleum refineries.

 


Status: Closed - Acceptable Action
Closed - Acceptable Action (C - AA) - The recipient has completed action on the recommendation. The action taken meets the objectives envisioned by the Board.
 

PDF Document Recommendation Status Change Summary

2012-03-I-CA-37

Revise the Richmond Industrial Safety Ordinance (RISO) regulations for petroleum refineries to require a process safety culture continuous improvement program including a written procedure for periodic process safety culture surveys across the work force. Require an oversight committee comprised of the regulator, the company, the company’s workforce and their representatives, and community representatives. This oversight committee shall:

a. Select an expert third party that will administer a periodic process safety culture survey;

b. Review and comment on the third party expert report developed from the survey;

c. Oversee the development and effective implementation of action items to effectively address identified process safety culture issues; and

d. Develop process safety culture indicators to measure major accident prevention performance.

The periodic process safety culture report shall be made available to the plant workforce.


Status: Closed - Acceptable Alternative Action
Closed - Acceptable Alternative Action (C - AAA)
 

PDF Document Recommendation Status Change Summary

CITGO Refinery Hydrofluoric Acid Release and Fire (2 Recommendations)
CITGO, Inc. (2 Recommendations)
Open: 0% | Closed: 100%

Final Report Released On: December 09, 2009

2009-14-I-TX-1 URGENT!

  • Within 30 days, develop and initiate actions to ensure adequate water supply to the CITGO HF mitigation system.  Actions could include, but are not limited to, increasing onsite storage capacity, installing a permanent backup system, and developing procedures and training for water management in an emergency.
  • Every 30 days, report actions planned or completed to the Refinery Terminal Fire Company and Local Emergency Planning Committee.  Continue the 30-day periodic reporting until all planned actions are fully implemented.


Status: Closed - Acceptable Action
Closed - Acceptable Action (C - AA) - The recipient has completed action on the recommendation. The action taken meets the objectives envisioned by the Board.
 

PDF Document Download

2009-14-I-TX-2 URGENT!

  • Within 60 days, complete a third-party audit of all (Corpus Christi, TX and Lemont, IL) CITGO HF alkylation unit operations in the United States as recommended by API Recommended Practice 751, Safe Operation of Hydrofluoric Acid Alkylation Units, Third Edition June 2007. The selected lead auditor shall have extensive knowledge of HF hazards, HF alkylation units, and API 751. 
  • Consistent with the employee participation requirements of the Process Safety Management Standard for Highly Hazardous Chemicals (29 CFR 1910.119(c)), share all audit results and actions planned or completed to correct deficiencies in each refinery with all CITGO and contract employees whose work area includes that refinery’s alkylation unit.


Status: Closed - Acceptable Action
Closed - Acceptable Action (C - AA) - The recipient has completed action on the recommendation. The action taken meets the objectives envisioned by the Board.
 

PDF Document Download

Combustible Dust Hazard Investigation (6 Recommendations)
American National Standards Institute (ANSI) Z400.1 Committee (1 Recommendations)
Open: 0% | Closed: 100%

Final Report Released On: November 09, 2006

2006-1-H-6

Modify ANSI Z400.1 American National Standard for Hazardous Industrial Chemicals--Material Safety Data Sheets to recommend that MSDSs include information on: - combustible dust hazards, safe handling practices, and references to relevant fire codes in MSDS; - hazard information about the by-products of materials that may generate combustible dusts due to processing or handling; - identification of combustible dust hazards and selection of physical properties to include in MSDS.


Status: Closed - Acceptable Action
Closed - Acceptable Action (C - AA) - The recipient has completed action on the recommendation. The action taken meets the objectives envisioned by the Board.
 

Occupational Safety and Health Administration (OSHA) (5 Recommendations)
Open: 0% | Closed: 100%

Final Report Released On: November 09, 2006

2006-1-H-1

(Superseded by 2017-07-I-WI-R10 from the Didion Milling Co. investigation)

Issue a standard designed to prevent combustible dust fires and explosions in general industry. Base the standard on current National Fire Protection Association (NFPA) dust explosion standards (including NFPA 654 and NFPA 484), and include at least - hazard assessment, - engineering controls, - housekeeping, - building design, - explosion protection, - operating procedures, and - worker training.


Status: Closed - Reconsidered/Superseded
Closed - Reconsidered/Superseded (C - R/S) - Recipient rejects the recommendation and also supports the rejection with a rationale with which the Board concurs. This designation may apply when later facts indicate that the concerns expressed in the recommendation were actually addressed prior to the incident, or when a recommendation is superseded by a new, more appropriate recommendation.
 

PDF Document Recommendation Status Change Summary

2006-1-H-2

Revise the Hazard Communication Standard (HCS) (1910.1200) to: - Clarify that the HCS covers combustible dusts, including those materials that may reasonably be anticipated to generate combustible dusts through downstream processing or handling. - Require Material Safety Data Sheets (MSDSs) to include the hazards and physical properties of combustible dusts, as well as clear information on safe handling practices and references to relevant consensus standards.


Status: Closed - Acceptable Action
Closed - Acceptable Action (C - AA) - The recipient has completed action on the recommendation. The action taken meets the objectives envisioned by the Board.
 

PDF Document Recommendations Status Change Summary

2006-1-H-3

Communicate to the United Nations Economic Commission for Europe (UNECE) the need to amend the Globally Harmonized System (GHS) to address combustible dust hazards by: - defining combustible dusts, - specifying the hazards that must be addressed in chemical information sheets, and - addressing the physical properties that must be included on a chemical information sheet pertinent to combustible dusts.


Status: Closed - Acceptable Action
Closed - Acceptable Action (C - AA) - The recipient has completed action on the recommendation. The action taken meets the objectives envisioned by the Board.
 

2006-1-H-4

Provide training through the OSHA Training Institute (OTI) on recognizing and preventing combustible dust explosions.


Status: Closed - Acceptable Action
Closed - Acceptable Action (C - AA) - The recipient has completed action on the recommendation. The action taken meets the objectives envisioned by the Board.
 

2006-1-H-5

While a standard is being developed, identify manufacturing industries at risk and develop and implement a national Special Emphasis Program (SEP) on combustible dust hazards in general industry. Include in the SEP an outreach program focused on the information in the Safety and Health Information Bulletin (SHIB), Combustible Dust in Industry: Preventing and Mitigating the Effects of Fire and Explosions.


Status: Closed - Acceptable Action
Closed - Acceptable Action (C - AA) - The recipient has completed action on the recommendation. The action taken meets the objectives envisioned by the Board.
 

ConAgra Natural Gas Explosion and Ammonia Release (4 Recommendations)
American Gas Association (AGA) (1 Recommendations)
Open: 0% | Closed: 100%

Final Report Released On: February 04, 2010

2010-12-I-NC-1 URGENT!

Enact a Tentative Interim Amendment as well as permanent changes to the National Fuel Gas Code (NFPA 54/ANSI Z223.1) to require that during the purging of fuel gas piping at industrial, commercial, and public facilities: (a) Purged fuel gases shall be directly vented to a safe location outdoors, away from personnel and ignition sources 

(b) If it is not possible to vent purged gases outdoors, purging gas to the inside of a building shall be allowed only upon approval by the authority having jurisdiction of a documented risk evaluation and hazard control plan. The evaluation and plan shall establish that indoor purging is necessary and that adequate safeguards are in place such as:

     • Evacuating nonessential personnel from the vicinity of the purging;      • Providing adequate ventilation to maintain the gas concentration at an established safe level, substantially below   
     the lower explosive limit; and

     • Controlling or eliminating potential ignition sources
(c) Combustible gas detectors are used to continuously monitor the gas concentration at appropriate locations in the vicinity where purged gases are released

(d) Personnel are trained about the problems of odor fade and odor fatigue and warned against relying on odor alone for detecting releases of fuel gases


Status: Closed - Acceptable Action
Closed - Acceptable Action (C - AA) - The recipient has completed action on the recommendation. The action taken meets the objectives envisioned by the Board.
 

PDF Document Download

ICC International Fuel Gas Code Committee Chair (1 Recommendations)
Open: 0% | Closed: 100%

Final Report Released On: February 04, 2010

2010-12-I-NC-2 URGENT!

Incorporate the revised gas purging provisions of the National Fuel Gas Code, consistent with CSB recommendation 2009-12-I-NC-R1, into the International Fuel Gas Code


Status: Closed - Acceptable Action
Closed - Acceptable Action (C - AA) - The recipient has completed action on the recommendation. The action taken meets the objectives envisioned by the Board.
 

PDF Document Download

International Code Council (ICC) (1 Recommendations)
Open: 0% | Closed: 100%

Final Report Released On: February 04, 2010

2010-12-I-NC-2 URGENT!

Incorporate the revised gas purging provisions of the National Fuel Gas Code, consistent with CSB recommendation 2009-12-I-NC-R1, into the International Fuel Gas Code


Status: Closed - Acceptable Action
Closed - Acceptable Action (C - AA) - The recipient has completed action on the recommendation. The action taken meets the objectives envisioned by the Board.
 

PDF Document Download

National Fire Protection Association (NFPA) (1 Recommendations)
Open: 0% | Closed: 100%

Final Report Released On: February 04, 2010

2010-12-I-NC-1 URGENT!

Enact a Tentative Interim Amendment as well as permanent changes to the National Fuel Gas Code (NFPA 54/ANSI Z223.1) to require that during the purging of fuel gas piping at industrial, commercial, and public facilities: (a) Purged fuel gases shall be directly vented to a safe location outdoors, away from personnel and ignition sources 

(b) If it is not possible to vent purged gases outdoors, purging gas to the inside of a building shall be allowed only upon approval by the authority having jurisdiction of a documented risk evaluation and hazard control plan. The evaluation and plan shall establish that indoor purging is necessary and that adequate safeguards are in place such as:

     • Evacuating nonessential personnel from the vicinity of the purging;      • Providing adequate ventilation to maintain the gas concentration at an established safe level, substantially below   
     the lower explosive limit; and

     • Controlling or eliminating potential ignition sources
(c) Combustible gas detectors are used to continuously monitor the gas concentration at appropriate locations in the vicinity where purged gases are released

(d) Personnel are trained about the problems of odor fade and odor fatigue and warned against relying on odor alone for detecting releases of fuel gases


Status: Closed - Acceptable Action
Closed - Acceptable Action (C - AA) - The recipient has completed action on the recommendation. The action taken meets the objectives envisioned by the Board.
 

PDF Document Download