EQ Hazardous Waste Plant Explosions and Fire
Location: Apex, NC
Accident Occurred On: 10/05/2006
Final Report Released On: 04/16/2008
Accident Type: Community Impact
Company Name: EQ

statistics

Total # of Recommendations
6
Total # of Open Recommendations
0
Total # of Closed Recommendations
6
Total % of Open 0 vs. Closed 100

investigation information

Image
Accident Description
Explosions and fire at a hazardous waste facility forced the evacuation of approximately 16,000 residents from Apex, North Carolina, on October 5, 2006. The incident likely began in the oxidizer section of the EQ North Carolina waste facility, where chemicals such as pool chlorination tablets were stored. The fire was allowed to burn out and the facility was destroyed.
Investigation Status
The CSB's final report was issued at a news conference on April 16, 2008.


 

Recommendations

Environmental Protection Agency (EPA)
2007-1-I-NC-1

Ensure that the emergency response planning required for permitted hazardous waste treatment, storage, and disposal facilities (40 CFR 264.37) includes providing written information to state and local emergency response officials on the type, approximate quantities, and locations of materials within the facility (similar to reporting requirements of the Emergency Planning and Community Right-to-Know Act). Additionally, ensure that permit holders periodically update this information throughout the ten-year permit period.

Status: Closed - Acceptable Action
Closed - Acceptable Action (C - AA) - The recipient has completed action on the recommendation. The action taken meets the objectives envisioned by the Board.
 

Environmental Technology Council
2007-1-I-NC-2

Petition the National Fire Protection Association, following the guidelines of their "Codes and Standards Development Process" (http://www.nfpa.org/index.asp), to develop a fire protection standard (occupancy standard) specific to hazardous waste treatment, storage, and disposal facilities. This standard should address fire prevention, detection, control, and suppression requirements.

Note:  This recommendation was superseded by 2009-10-I-OH-R6, issued pursuant to the Veolia Environmental Services Flammable Vapor Explosion and Fire Case Study (2010).

 

Status: Closed - Reconsidered/Superseded
Closed - Reconsidered/Superseded (C - R/S) - Recipient rejects the recommendation and also supports the rejection with a rationale with which the Board concurs. This designation may apply when later facts indicate that the concerns expressed in the recommendation were actually addressed prior to the incident, or when a recommendation is superseded by a new, more appropriate recommendation.
 

2007-1-I-NC-3

Develop standardized guidance for the handling and storage of hazardous waste to reduce the likelihood of releases and fires at hazardous waste treatment, storage, and disposal facilities.

Note:  This recommendation was superseded by 2009-10-I-OH-R7, issued pursuant to the Veolia Environmental Services Flammable Vapor Explosion and Fire Case Study (2010).

Status: Closed - Reconsidered/Superseded
Closed - Reconsidered/Superseded (C - R/S) - Recipient rejects the recommendation and also supports the rejection with a rationale with which the Board concurs. This designation may apply when later facts indicate that the concerns expressed in the recommendation were actually addressed prior to the incident, or when a recommendation is superseded by a new, more appropriate recommendation.
 

Mobile Aerospace Engineering, Inc.
2007-1-I-NC-1

Revise and or develop company procedures and policies to require and ensure that unspent chemical oxygen generators that have exceeded their service life be actuated so that the chemical core is expended before shipping by any transport mode.

URGENT!
Status: Closed - Acceptable Action
Closed - Acceptable Action (C - AA) - The recipient has completed action on the recommendation. The action taken meets the objectives envisioned by the Board.
 

Download
2007-1-I-NC-2

Review and revise as necessary company procedures and policies for transporting hazardous waste to ensure that hazardous waste is correctly characterized on the shipping manifest.

URGENT!
Status: Closed - Acceptable Action
Closed - Acceptable Action (C - AA) - The recipient has completed action on the recommendation. The action taken meets the objectives envisioned by the Board.
 

2007-1-I-NC-3

Communicate to all of your waste brokers and treatment, storage, and disposal facilities to which unspent oxygen generators were shipped: - the hazards associated with unspent chemical oxygen generators and - that the incorrect shipping name and UN code was, or might have been used, for unspent chemical oxygen generators shipped from your facility.

URGENT!
Status: Closed - Acceptable Action
Closed - Acceptable Action (C - AA) - The recipient has completed action on the recommendation. The action taken meets the objectives envisioned by the Board.
 

 
 

Related Video

Emergency in Apex
4/16/2008 4:00:00 AM
A North Carolina town is evacuated when fire engulfs a hazardous waste depot. read more

Download QuickTime Video

Related News

Apex_Fire_pic_1737_hours_003_rev
CSB Issues New Safety Video on Hazardous Waste Facility Fire in Apex, NC
4/16/2008
The U.S. Chemical Safety Board (CSB) today released its latest safety video to accompany the CSB's final report on the October 2006 hazardous waste fire and community evacuation in Apex, North Carolina.
read more
P1000221
Final CSB Report on EQ Hazardous Waste Fire and Community Evacuation in Apex Calls for New Fire Protection Standards, Improved Chemical Information for Emergency Planners
4/16/2008
In a case study report released today on the October 2006 hazardous waste fire at the Environmental Quality Company (EQ), the U.S. Chemical Safety Board (CSB) called for a new national fire code for hazardous waste facilities and for improving the information provided to community emergency planners about the chemicals those facilities store and handle.