The CSB issues safety recommendations to prevent the recurrence or reduce the likelihood or consequences of similar incidents or hazards in the future. Recommendations are issued to a variety of parties, including government entities, safety organizations, trade unions, trade associations, corporations, emergency response organizations, educational institutions, and public interest groups. Recommendations are published in CSB reports and are closed only by vote of the Board. The CSB tracks all recommendations and communicates regularly with recommendations recipients to ensure that the recommended corrective actions are implemented.

For more information, see Frequently Asked Questions about CSB recommendations.


Quick Search

 
Recommendations Status:
 
 
Expand All

Recommendations

Acetylene Service Company Gas Explosion (5 Recommendations)
Acetylene Service Company (ASCO) (2 Recommendations)
Open: 0% | Closed: 100%

Final Report Released On: January 25, 2006

2005-3-I-NJ-1

Improve isolation on acetylene generator water lines by incorporating a double-block-and-bleed with a vent to a safe location, or other isolation means of comparable effectiveness.


Status: Closed - No Longer Applicable
Closed - No Longer Applicable (C - NLA) - Due to subsequent events, the recommendation action no longer applies (e.g., the facility was destroyed or the company went out of business).
 

2005-3-I-NJ-2

Implement an effective Process Safety Management program, in accordance with OSHA 1910.119. Include written operating procedures and checklists that are understood by the workers responsible for using them. Train workers on the procedures and periodically confirm that they are being properly followed.


Status: Closed - No Longer Applicable
Closed - No Longer Applicable (C - NLA) - Due to subsequent events, the recommendation action no longer applies (e.g., the facility was destroyed or the company went out of business).
 

Occupational Safety and Health Administration (OSHA) (1 Recommendations)
Open: 0% | Closed: 100%

Final Report Released On: January 25, 2006

2005-3-I-NJ-5

Update the OSHA 1910.102 Acetylene Standard (a. Cylinders, b. Piped Systems, and c. Generators and filling cylinders) to remove the existing references to unavailable and obsolete Compressed Gas Association Pamphlets (CGA G-1-1966, G 1.3-1959, G 1.4-1966). As an alternative, consider incorporating by reference NFPA 51A Standard for Acetylene Cylinder Charging Plants.


Status: Closed - Acceptable Action
Closed - Acceptable Action (C - AA) - The recipient has completed action on the recommendation. The action taken meets the objectives envisioned by the Board.
 

Rexarc, Inc. (2 Recommendations)
Open: 0% | Closed: 100%

Final Report Released On: January 25, 2006

2005-3-I-NJ-3

Immediately inform existing acetylene generator users that the check valve did not prevent acetylene gas backflow in this incident. Recommend interim actions be taken to ensure that Rexarc check valves in service on acetylene production equipment will operate reliably.


Status: Closed - Acceptable Action
Closed - Acceptable Action (C - AA) - The recipient has completed action on the recommendation. The action taken meets the objectives envisioned by the Board.
 

PDF Document Download

2005-3-I-NJ-4

Replace check valves of this or similar design supplied by Rexarc with valves that will perform more reliably in recycle water service.


Status: Closed - Acceptable Action
Closed - Acceptable Action (C - AA) - The recipient has completed action on the recommendation. The action taken meets the objectives envisioned by the Board.
 

PDF Document Download