UPDATED - Jacksonville, Florida, 7:15 p.m., September 15, 2009 - At a public meeting here tonight, the Board voted unanimously to approve the draft report on the fire and explosion at T2 Laboratories.
Jacksonville, Florida, September 15, 2009 – The massive December 2007 explosion and fire at T2 Laboratories in Jacksonville was caused by a runaway chemical reaction that likely resulted from an inadequate reactor cooling system, investigators from the U.S. Chemical Safety Board (CSB) said in a final draft report released today. The Board is to vote on the report findings and recommendations at a public meeting in Jacksonville this evening.
Concluding that T2 did not recognize all of the potential hazards of the process for making a gasoline additive, the report calls for improving the education of chemical engineering students on reactive chemical hazards. The explosion and fire on December 19, 2007, killed four T2 employees and injured four others. In addition, 28 people working at nearby businesses were injured when building walls and windows blew in. The blast sent debris up to a mile away and damaged buildings within a quarter-mile of the facility.
“This is one of the largest reactive chemical accidents the CSB has investigated,” said Chairman John Bresland. “We hope our findings once again call attention to the need for companies to be aware of how to control reactive chemical hazards.” In 2002 the CSB completed a study of reactive chemical hazards, which identified 167 accidents over a two-decade period and made recommendations to improve reactive chemical safety.
The draft report on the T2 Laboratories explosion calls on the American Institute of Chemical Engineers (AIChE) and the Accreditation Board for Engineering and Technology (ABET) to work together to include reactive chemical education in baccalaureate chemical engineering curricula across the country.
The CSB found that although the two owners of the company had undergraduate degrees in chemistry and chemical engineering, they were nonetheless likely unaware of the potential or the consequences of a runaway chemical reaction. The CSB noted that most baccalaureate chemical engineering curricula in the U.S. do not specifically address reactive hazard recognition or management.
Chairman Bresland said, “It’s important that chemical engineers recognize and are aware of the proper management of reactive hazards.”
Investigation Supervisor Robert Hall, PE, said, “Our recommendations aim to address the gap in the chemical engineering curriculum. If future chemical engineers are given the proper educational tools, they will be able to more fully comprehend the hazards that exist during a chemical manufacturing process.”
The draft report and safety recommendations will be considered for approval by the Board at a public meeting tonight in Jacksonville. The meeting will begin at 6:00 p.m. at the Marriott Hotel located at 4670 Salisbury Road. All findings, causes, and recommendations remain preliminary pending approval by the Board. The Board will ask for public comments on the investigation at the public meeting.
The CSB also today released a 3-D computer animation depicting the events that led to the accident. Following approval of the report, the CSB plans to release a new nine-minute safety video, “Runaway: Explosion at T2 Laboratories,” containing the 3-D computer animation and a description of the causes, consequences, lessons, and recommendations resulting from the accident.
The accident occurred during T2’s production of MCMT, a gasoline additive, which the company manufactured in batches using a 2500-gallon reactor. On the day of the accident T2 was producing its 175th batch of the chemical when operators reported a cooling problem.
Mr. Hall said, “Despite a number of near-misses during earlier production efforts, T2 failed to recognize the underlying runaway reaction hazard associated with its manufacturing process.”
Chemical testing by the CSB found that the recipe used by T2 created two exothermic, or heat-producing, reactions; the first was an intended part of producing MCMT but the second, undesired reaction occurred if the temperature went above 390ºF, slightly higher than the normal production temperature. The cooling system likely malfunctioned due to a blockage in the water supply piping or a valve failure. The temperature and pressure inside the reactor began to rise uncontrollably in a runaway chemical reaction. At 1:33 pm, approximately ten minutes after the initial cooling problem was reported, the reactor burst and its contents exploded.
The CSB is an independent federal agency charged with investigating industrial chemical accidents. The agency’s board members are appointed by the president and confirmed by the Senate. CSB investigations look into all aspects of chemical accidents, including physical causes such as equipment failure as well as inadequacies in regulations, industry standards, and safety management systems.
The Board does not issue citations or fines but does make safety recommendations to companies, industry organizations, labor groups, and regulatory agencies such as OSHA and EPA. Please visit our website, www.csb.gov.
For more information please contact Public Affairs Director Daniel Horowitz at (202) 441-6074 (cell); Sandy Gilmour (202) 251-5496 (cell); or Public Affairs Specialist Hillary Cohen at (202) 446-8094 (cell).