The CSB issues safety recommendations to prevent the recurrence or reduce the likelihood or consequences of similar incidents or hazards in the future. Recommendations are issued to a variety of parties, including government entities, safety organizations, trade unions, trade associations, corporations, emergency response organizations, educational institutions, and public interest groups. Recommendations are published in CSB reports and are closed only by vote of the Board. The CSB tracks all recommendations and communicates regularly with recommendations recipients to ensure that the recommended corrective actions are implemented.

For more information, see Frequently Asked Questions about CSB recommendations.


Quick Search

 
Recommendations Status:
 
 
Expand All

Recommendations

Barton Solvents Explosions and Fire (9 Recommendations)
American Chemistry Council (ACC) (1 Recommendations)
Open: 0% | Closed: 100%

Final Report Released On: June 26, 2008

2007-6-I-KS-4

Recommend to your membership companies that prepare MSDSs to update the MSDSs to: -Identify and include a warning for materials that are static accumulators and that may form ignitable vapor-air mixtures in storage tanks. -Include a statement that bonding and grounding may be insufficient to eliminate the hazard from static-accumulating flammable liquids, and provide examples of additional precautions and references to the relevant consensus guidance (e.g., NFPA 77, Recommended Practice on Static Electricity (2007), and API Recommended Practice 2003, Protection Against Ignitions Arising Out of Static, Lightning, and Stray Currents (2008)). -Include conductivity testing data for the materials that are static accumulators and that may form ignitable vapor-air mixtures in storage tanks.


Status: Closed - Acceptable Action
Closed - Acceptable Action (C - AA) - The recipient has completed action on the recommendation. The action taken meets the objectives envisioned by the Board.
 

American National Standards Institute (ANSI) Z400.1 Committee (1 Recommendations)
Open: 0% | Closed: 100%

Final Report Released On: June 26, 2008

2007-6-I-KS-3

Revise ANSI Z400.1 to advise chemical manufacturers and importers that prepare MSDSs to: -Identify and include a warning for materials that are static-accumulators and that may form ignitable vapor-air mixtures in storage tanks; -Advise users that bonding and grounding may be insufficient to eliminate the hazard from static-accumulating flammable liquids, and provide examples of additional precautions and references to the relevant consensus guidance (e.g., NFPA 77, Recommended Practice on Static Electricity (2007), and API Recommended Practice 2003, Protection Against Ignitions Arising Out of Static, Lightning, and Stray Currents (2008)); and -Provide conductivity testing data for materials that are static accumulators and that may form ignitable vapor-air mixtures in storage tanks.


Status: Closed - Acceptable Action
Closed - Acceptable Action (C - AA) - The recipient has completed action on the recommendation. The action taken meets the objectives envisioned by the Board.
 

American Petroleum Institute (API) (1 Recommendations)
Open: 0% | Closed: 100%

Final Report Released On: June 26, 2008

2007-6-I-KS-5

Recommend to your membership companies that prepare MSDSs to update the MSDSs to: -Identify and include a warning for materials that are static accumulators and that may form ignitable vapor-air mixtures in storage tanks. -Include a statement that bonding and grounding may be insufficient to eliminate the hazard from static-accumulating flammable liquids, and provide examples of additional precautions and references to the relevant consensus guidance (e.g., NFPA 77, Recommended Practice on Static Electricity (2007), and API Recommended Practice 2003, Protection Against Ignitions Arising Out of Static, Lightning, and Stray Currents (2008)). -Include conductivity testing data for the materials that are static accumulators and that may form ignitable vapor-air mixtures in storage tanks.


Status: Closed - Acceptable Action
Closed - Acceptable Action (C - AA) - The recipient has completed action on the recommendation. The action taken meets the objectives envisioned by the Board.
 

National Association of Chemical Distributors (NACD) (1 Recommendations)
Open: 0% | Closed: 100%

Final Report Released On: June 26, 2008

2007-6-I-KS-6

Recommend to your membership companies that prepare MSDSs to update the MSDSs to: -Identify and include a warning for materials that are static accumulators and that may form ignitable vapor-air mixtures in storage tanks. -Include a statement that bonding and grounding may be insufficient to eliminate the hazard from static-accumulating flammable liquids, and provide examples of additional precautions and references to the relevant consensus guidance (e.g., NFPA 77, Recommended Practice on Static Electricity (2007), and API Recommended Practice 2003, Protection Against Ignitions Arising Out of Static, Lightning, and Stray Currents (2008)). -Include conductivity testing data for the materials that are static accumulators and that may form ignitable vapor-air mixtures in storage tanks.


Status: Closed - Acceptable Action
Closed - Acceptable Action (C - AA) - The recipient has completed action on the recommendation. The action taken meets the objectives envisioned by the Board.
 

National Paint and Coatings Association (NPCA) (1 Recommendations)
Open: 0% | Closed: 100%

Final Report Released On: June 26, 2008

2007-6-I-KS-7

Recommend to your membership companies that prepare MSDSs to update the MSDSs to: -Identify and include a warning for materials that are static accumulators and that may form ignitable vapor-air mixtures in storage tanks. -Include a statement that bonding and grounding may be insufficient to eliminate the hazard from static-accumulating flammable liquids, and provide examples of additional precautions and references to the relevant consensus guidance (e.g., NFPA 77, Recommended Practice on Static Electricity (2007), and API Recommended Practice 2003, Protection Against Ignitions Arising Out of Static, Lightning, and Stray Currents (2008)). -Include conductivity testing data for the materials that are static accumulators and that may form ignitable vapor-air mixtures in storage tanks.


Status: Closed - Acceptable Action
Closed - Acceptable Action (C - AA) - The recipient has completed action on the recommendation. The action taken meets the objectives envisioned by the Board.
 

National Petrochemical and Refiners Association (NPRA) (1 Recommendations)
Open: 0% | Closed: 100%

Final Report Released On: June 26, 2008

2007-6-I-KS-8

Recommend to your membership companies that prepare MSDSs to update the MSDSs to: -Identify and include a warning for materials that are static accumulators and that may form ignitable vapor-air mixtures in storage tanks. -Include a statement that bonding and grounding may be insufficient to eliminate the hazard from static-accumulating flammable liquids, and provide examples of additional precautions and references to the relevant consensus guidance (e.g., NFPA 77, Recommended Practice on Static Electricity (2007), and API Recommended Practice 2003, Protection Against Ignitions Arising Out of Static, Lightning, and Stray Currents (2008)). -Include conductivity testing data for the materials that are static accumulators and that may form ignitable vapor-air mixtures in storage tanks.


Status: Closed - Acceptable Action
Closed - Acceptable Action (C - AA) - The recipient has completed action on the recommendation. The action taken meets the objectives envisioned by the Board.
 

Occupational Safety and Health Administration (OSHA) (2 Recommendations)
Open: 50% | Closed: 50%

Final Report Released On: June 26, 2008

2007-6-I-KS-1

Revise the "Guidance for Hazard Determination for compliance with the OSHA Hazard Communication Standard" to advise chemical manufacturers and importers that prepare MSDSs to: -Evaluate flammable liquids to determine their potential to accumulate static electricity and form ignitable vapor-air mixtures in storage tanks. -Test the conductivity of the flammable liquid and include the testing results in the MSDS.


Status: Open - Acceptable Response or Alternate Response
Open - Acceptable Response or Alternate Response (O - ARAR) - Response from recipient indicates a planned action that would satisfy the objective of the recommendation when implemented.
 

2007-6-I-KS-2

Prior to the next revision, communicate to the Sub-Committee on the Globally Harmonized System of Classification and Labeling of Chemicals (SCEGHS) the need to amend the GHS to advise chemical manufacturers and importers that prepare MSDSs to: -Identify and include a warning for materials that are static accumulators and that may form ignitable vapor-air mixtures in storage tanks. -Advise users that bonding and grounding may be insufficient to eliminate the hazard from static-accumulating flammable liquids, and provide examples of additional precautions and references to the relevant consensus guidance (e.g., NFPA 77, Recommended Practice on Static Electricity (2007), and API Recommended Practice 2003, Protection Against Ignitions Arising Out of Static, Lightning, and Stray Currents (2008)). -Provide conductivity testing data for materials that are static accumulators and that may form ignitable vapor-air mixtures in storage tanks.


Status: Closed - Acceptable Action
Closed - Acceptable Action (C - AA) - The recipient has completed action on the recommendation. The action taken meets the objectives envisioned by the Board.
 

PDF Document Recommendation Status Change Summary

Society for Chemical Hazard Communication (SCHC) (1 Recommendations)
Open: 0% | Closed: 100%

Final Report Released On: June 26, 2008

2007-6-I-KS-9

Recommend to your membership companies that prepare MSDSs to update the MSDSs to: -Identify and include a warning for materials that are static accumulators and that may form ignitable vapor-air mixtures in storage tanks. -Include a statement that bonding and grounding may be insufficient to eliminate the hazard from static-accumulating flammable liquids, and provide examples of additional precautions and references to the relevant consensus guidance (e.g., NFPA 77, Recommended Practice on Static Electricity (2007), and API Recommended Practice 2003, Protection Against Ignitions Arising Out of Static, Lightning, and Stray Currents (2008)). -Include conductivity testing data for the materials that are static accumulators and that may form ignitable vapor-air mixtures in storage tanks.


Status: Closed - Acceptable Action
Closed - Acceptable Action (C - AA) - The recipient has completed action on the recommendation. The action taken meets the objectives envisioned by the Board.