The CSB issues safety recommendations to prevent the recurrence or reduce the likelihood or consequences of similar incidents or hazards in the future. Recommendations are issued to a variety of parties, including government entities, safety organizations, trade unions, trade associations, corporations, emergency response organizations, educational institutions, and public interest groups. Recommendations are published in CSB reports and are closed only by vote of the Board. The CSB tracks all recommendations and communicates regularly with recommendations recipients to ensure that the recommended corrective actions are implemented.

For more information, see Frequently Asked Questions about CSB recommendations.


Quick Search

 
Recommendations Status:
 
 
Expand All

Recommendations

Barton Solvents Explosions and Fire (1 Recommendations)
Occupational Safety and Health Administration (OSHA) (1 Recommendations)
Open: 100% | Closed: 0%

Final Report Released On: June 26, 2008

2007-6-I-KS-1

Revise the "Guidance for Hazard Determination for compliance with the OSHA Hazard Communication Standard" to advise chemical manufacturers and importers that prepare MSDSs to: -Evaluate flammable liquids to determine their potential to accumulate static electricity and form ignitable vapor-air mixtures in storage tanks. -Test the conductivity of the flammable liquid and include the testing results in the MSDS.


Status: Open - Acceptable Response or Alternate Response
Open - Acceptable Response or Alternate Response (O - ARAR) - Response from recipient indicates a planned action that would satisfy the objective of the recommendation when implemented.
 

BP America (Texas City) Refinery Explosion (1 Recommendations)
Occupational Safety and Health Administration (OSHA) (1 Recommendations)
Open: 100% | Closed: 0%

Final Report Released On: March 20, 2007

2005-4-I-TX-9

2. Amend the OSHA PSM standard to require that a management of change (MOC) review be conducted for organizational changes that may impact process safety including: a. major organizational changes such as mergers, acquisitions, or reorganizations; b. personnel changes, including changes in staffing levels or staff experience; and c. policy changes such as budget cutting.


Status: Open - Unacceptable Response/No Response Received
Open - Unacceptable Response/No Response Received (O - UR) - Recipient responds by expressing disagreement with the need outlined in the recommendation. The Board believes, however, that there is enough supporting evidence to ask the recipient to reconsider.
 

PDF Document Download

DuPont Belle Toxic Chemical Releases (1 Recommendations)
Occupational Safety and Health Administration (OSHA) (1 Recommendations)
Open: 100% | Closed: 0%

Final Report Released On: September 20, 2011

2010-06-I-WV-2

Take sustained measures to minimize the exposure of hazards to workers handling highly toxic gases from cylinders and associated regulators, gages, hoses, and appliances. Ensure that OSHA managers, compliance officers, equivalent state OSHA plan personnel, and regulated parties conform, under the Process Safety Management Standard (29 CFR 1910.119) Recognized and Generally Accepted Good Engineering Practices (RAGAGEP) provisions, to industry practices at least as effective as the following:

  1. NFPA 55 - Compressed Gases and Cryogenic Fluids Code (2010)
  2. CGA P-1 Safe Handling of Compressed Gases in Containers (2008)
  3. CGA E-9 Standard for Flexible, PTFE-lined Pigtails for Compressed Gas Service (2010)
  4. ASME B31.3 Process Piping (2008)

 


Status: Open - Acceptable Response or Alternate Response
Open - Acceptable Response or Alternate Response (O - ARAR) - Response from recipient indicates a planned action that would satisfy the objective of the recommendation when implemented.
 

PDF Document Recommendation Status Change Summary

Improving Reactive Hazard Management (1 Recommendations)
Environmental Protection Agency (EPA) (1 Recommendations)
Open: 100% | Closed: 0%

Final Report Released On: October 08, 2002

2001-01-H-3

Revise the Accidental Release Prevention Requirements, 40 CFR 68, to explicitly cover catastrophic reactive hazards that have the potential to seriously impact the public, including those resulting from self-reactive chemicals and combinations of chemicals and process-specific conditions. Take into account the recommendations of this report to OSHA on reactive hazard coverage. Seek congressional authority if necessary to amend the regulation.


Status: Open - Acceptable Response or Alternate Response
Open - Acceptable Response or Alternate Response (O - ARAR) - Response from recipient indicates a planned action that would satisfy the objective of the recommendation when implemented.
 

PDF Document Recommendation Status Change Summary

Oil Tank Safety Study (1 Recommendations)
State of Oklahoma/Oklahoma Corporation Commission (1 Recommendations)
Open: 100% | Closed: 0%

Final Report Released On: October 27, 2011

2011-H-1-3

Amend state oil and gas regulations to:

a) Protect storage tanks at exploration and production sites from public access by requiring sufficient security measures, such as full fencing with a locked gate, hatch locks on tank manways, and barriers securely attached to tank external ladders and stairways.

b) Require hazards signs or placards on or near tanks that identify the fire and explosion hazards using words and symbols recognizable by the general public.

c) Require the use of inherently safer tank design features such as flame arrestors, pressure vacuum vents, floating roofs, vapor recovery systems or an equivalent alternative, to prevent the ignition of a flammable atmosphere inside the tank.


Status: Open - Acceptable Response or Alternate Response
Open - Acceptable Response or Alternate Response (O - ARAR) - Response from recipient indicates a planned action that would satisfy the objective of the recommendation when implemented.
 

PDF Document Recommendation Status Change Summary

Valero McKee Refinery Propane Fire (1 Recommendations)
American Petroleum Institute (API) (1 Recommendations)
Open: 100% | Closed: 0%

Final Report Released On: July 09, 2008

2007-5-I-TX-4

Revise API Standard 2510, Design and Construction of LPG Installations, and API Publication 2510A, Fire-Protection Considerations for the Design and Operation of Liquefied Petroleum Gas (LPG) Storage Facilities, to address effective deluge system activation during emergencies originating in nearby process units.


Status: Open - Acceptable Response or Alternate Response
Open - Acceptable Response or Alternate Response (O - ARAR) - Response from recipient indicates a planned action that would satisfy the objective of the recommendation when implemented.